1. Overview
HYFW Series Pole Mounted Load Break Switch is designed for tripping off and making load current or overload current in power system, and it is able to isolate the fault section in distribution network. HYFW series is applied in electricity distribution network of rated voltage 12kV, 24kV, 40.5kV, rated current 630A, frequency 50Hz or 60Hz. Equipped with controller of state of the art, HYFW series is viable for manual operation, electric operation and operation modes of local and remote. The cabinet made of stainless steel makes it possible for the controller to work under various environmental conditions. Wired or wireless modem are optional for remote monitoring and control. HYFW series is advantageous in budget, simple in structure, and easy in pole mounting.
2. Environmental Conditions
Surrounding Temperature: +50℃ to -40℃
Relative Humidity: 95%
Altitude: Less than 3000m
Wind Pressure: Less than 700pa (equals to velocity 34m/s)
Earthquake: 8 magnitude.
Mounting Area: Free from fire, explosion, corrosion and vibration.
Pollution Level: GradeⅢ, GradeⅣ
3. Features
▶SF6 Gas Insulation
SF6 is non-toxic, non-flammable insulation gas, with salient characteristic of arc extinguishing.
▶Variety of Bushing
Various options for bushing, besides the standard porcelain type, including the silicon rubber insulator for epoxy resin bushing.
▶Open/Closed State To Be Visible
Main contact indicator is clearly visible to the personnel on ground ( Green-Open, Red-Closed). The indicator is directly connected to main contact driving shaft to ensure that the indicator reflects the state of main contact accurately.
▶Fast Operation
Fast operations ( less than 1000ms) of opening and closing conducted by actuator with spring to store energy .
▶Operation Mode of Local or Remote
Both local operation and remote operation are viable, and remote operation by main console can be achieved through FTU/RTU panel.
▶Rugged Housing for Switchgear
The housing for switchgear is made of tough and anti-corrosion material (304L Stainless Steel) to provide long duration of lifetime (30 years), apt to a range of operations, with ideal characteristics for pole mounted device.
▶Standard
Each switchgear is filled with SF6 gas and hermetically sealed. Before leaving factory, each switchgear will be tested in accordance with criteria of IEC60265-1.
4. Model and Parameter
● Model of Product
● Technical Parameters
Description | Product Model | ||
HYFW-12 | HYFW-24 | HYFW-40.5 | |
Basic Characteristics | |||
Rated Voltage | 12kV | 24kV | 40.5kV |
Rated Current | 630A | 630A | 630A |
Rated Frequency | 50/60Hz | 50/60Hz | 50/60Hz |
Withstand Current for Short Duration | 20kA/4s | 20kA/4s | 20kA/4s |
Breaking Capacity | |||
Rated Active Load Breaking Current | 630A | 630A | 630A |
Number of Breaking Operation | 600 | 600 | 600 |
Making Current for Short Duration (Peak) | 50kA | 50kA | 50kA |
Number of Making Current for Short Duration Test | 5 | 5s | 5 |
Cable Charging Breaking Current | 25A | 25A | 25A |
Line Charging Breaking Current | 16A | 16A | 16A |
Rated Circuit Breaking Current | 630A | 630A | 630A |
Rated Off Load Transformer Breaking Current | 22A | 22A | 22A |
Power Frequency Withstand Voltage | |||
Phase to Phase, Phase to Earth, Between Open Contacts, 10s, Wet | 45kV | 50kV | 70kV |
Phase to Phase, Phase to Earth, 1 min, Dry | 50kV | 60kV | 95kV |
Between Open Contacts, 1 min, Dry | 50kV | 60kV | 110kV |
Lightning Impulse Withstand Voltage | |||
Phase to Earth | 85kV | 150kV | 195kV |
Between Open Contacts | 95kV | 150kV | 215kV |
Others | |||
Internal Arc Test | 20kA/0.1s | 20kA/0.1s | 20kA/0.1s |
Arc Extinguishing Medium | SF6 | SF6 | SF6 |
Insulation Medium | SF6 | SF6 | SF6 |
Creepage (Porcelain Bushing) | 380mm | 700mm | 1055mm |
Creepage (Silicon Rubber Bushing) | 540mm | 780mm | 1300mm |
Minimum Arcing Distance | 200mm | 290mm | 360mm |
Protection Level | IP65 | IP65 | IP65 |
Mechanical Characteristics | |||
Closing/Opening Time | <1s | <1s | <1s |
Number of Mechanical Operation | 10000 | 10000 | 10000 |
Ambient Environmental Temperature | -25~+70℃ | -25~+70℃ | -25~+70℃ |
Gas Pressure | |||
Rated Gas Pressure for Operation | 0.07MPa | 0.07MPa | 0.2MPa |
Actuation Gas Pressure for Anti-Explosion Device (MPa) | 0.4~0.6 MPa | 0.4~0.6 MPa | 0.4~0.6 MPa |
Minimum Gas Pressure For Operation (MPa) | 0.05MPa | 0.05MPa | 0.05MPa |
Gas Leakage Rate | ≤ 0.5% | ≤ 0.5% | ≤0.5% |